If you click the picture, You can see a large picture.
EX-CKL


MEX-CKL is mostly used at Semi conductor industry, Computer rooms, Standby power-generation facilities, where the system runs 24 hours and clean-water sensitive. Two ways of water dispersion system are available; gravity water spraying and pressurized spraying according to the site atmosphere.

 

High Efficient Fill   Nozzle sprayed water tend to flow inwardly by the airflow and the bottom corners become a dead areas of heat transfer. Our newly designed fill and its pitch arrangement technology minimize this drag and so increase the total thermal performance
Dual water distribution system   Let you blow evenly through the distribution system which added to cooling water in the spiral target Nozzle department Fill upper part of basin, and raise heat exchange efficiency.
WIDE AIR TRAVEL   Extend width of Fill.
The optimum design of air fluid.   Remove DEAD AREA of air fluid, and raise efficiency by the optimum contrariety of FAN and FILL.
High efficient Fan   High efficiency hollow aluminum fan blades are equipped as standard.

Adopt FAN CYLINDER formal PRESSURE RECOVERY FLARE.

Noise Level Table
MODEL COOLING
CAPACITY
CRT
WATER
FLOW
§©/hr
OVERALL DIMENSIONS(mm) FAN SPRAY
PUMP
KW x Q'TY
PIPING DIA. A x Q'TY COIL
Pd
mAq
WEIGHT kg
L W H ¦Dmm
x Q'TY
MOTOR
KW x Q'TY
CIR. WATER OVER
FLOW
DRAIN MAKE-UP DEAD OPERA-
TING
INLET OUTLET AUTO MANUAL
EX-60CKL 60 46.8 1750 3870 2980 1500x1 3.7x1 2.2x1 100x1 100x1 50x1 50x1 20x1 20x1 7.0 1650 2880
EX-80CKL 80 62.4 2050 4070 3090 1700x1 5.5x1 2.2x1 100x1 100x1 50x1 50x1 20x1 20x1 7.4 1950 3380
EX-100CKL 100 78 2050 4070 3590 1700x1 5.5x1 2.2x1 125x1 125x1 50x1 50x1 20x1 20x1 7.4 2390 3930
EX-125CKL 125 97.5 2050 4070 3590 1700x1 7.5x1 2.2x1 125x1 125x1 50x1 50x1 20x1 20x1 7.6 2550 4300
EX-150CKL 150 117 2400 4370 3630 2000x1 7.5x1 3.7x1 150x1 150x1 65x1 65x1 32x1 32x1 7.2 2950 4950
EX-200CKL 200 156 4100 4070 3590 1700x2 5.5x2 2.2x2 125x2 125x2 50x2 50x2 20x2 20x2 7.4 4780 7860
EX-250CKL 250 195 4100 4070 3590 1700x2 7.5x2 2.2x2 125x2 125x2 50x2 50x2 20x2 20x2 7.6 5100 8600
EX-300CKL 300 234 4800 4370 3630 2000x2 7.5x2 3.7x2 150x2 150x2 65x2 65x2 32x2 32x2 7.2 5900 9900
EX-375CKL 375 292.5 6150 4070 3590 1700x3 7.5x3 2.2x3 125x3 125x3 50x3 50x3 20x3 20x3 7.6 7650 12900
EX-400CKL 400 312 8200 4070 3590 1700x4 5.5x4 2.2x4 125x4 125x4 50x4 50x4 20x4 20x4 7.2 9560 15720
EX-450CKL 450 351 7200 4370 3630 2000x3 7.5x3 3.7x3 150x3 150x3 65x3 65x3 32x3 32x3 7.2 8850 14850
EX-500CKL 500 390 8200 4070 3590 1700x4 7.5x4 2.2x4 125x4 125x4 50x4 50x4 20x4 20x4 7.6 10200 17200
EX-600CKL 600 468 9600 4370 3630 2000x4 7.5x4 3.7x4 150x4 150x4 65x4 65x4 32x4 32x4 7.2 11800 19800
EX-750CKL 750 585 12000 4370 3630 2000x5 7.5x5 3.7x5 150x5 150x5 65x5 65x5 32x5 32x5 7.2 14750 24750
Table Note : Water flow & CRT are based upon 37¡É HWT, 32¡É CWT, 27¡É WBT and 0.78§©/h CR
 
 
Noise Level Table
UNIT : dB(A)

Measuring point

¨ç

¨è

¨é

¨ê

¨ë

¨ì

Measuring point ¨ç
Dm

Measuring distance

Dm

2m

5m

10m

20m

45° upper
Dfm

Model

Direction

EX-60CKL

W/L

67.5/61 67/63 64/59 59.5/53.5 54/48 73/72 1.8/3.9
EX-80CKL

W/L

68/61.5 68/64 65/60 60.5/54.5 55/49 73/73 2.1/4.1
EX-100CKL

W/L

69.5/63 70/66 67/62 60.5/57 57/51.5 75/75 2.1/4.1
EX-125CKL W/L 69.5/63 70/66 67/62 60.5/57 57/51.5 75/75 2.1/4.1
EX-150CKL

W/L

69.5/63 70/66 67/62 60.5/57 57/51.5 75/75 2.4/4.4
EX-200CKL

W/L

69.5/64 71.5/65.5 68.5/62.5 64/57 58.5/51.5 76/74 4.1/4.1
EX-250CKL

W/L

69.5/64 71.5/65.5 68.5/62.5 64/57 58.5/51.5 76/74 4.1/4.1
EX-300CKL

W/L

69/64 72/67 69/63 64.5/58 59/52.5 77/75 4.8/4.4
EX-375CKL

W/L

69/65.5 73/68 70/64 65.5/58.5 60/53 78/76 6.2/4.1
EX-400CKL

W/L

68/65.5 73/68 70/64 65.5/58.5 60/53 78/76 8.2/4.1
EX-450CKL

W/L

67/64 72/62 69/63 65/58 60/53 78/76 7.2/4.4
EX-500CKL

W/L

68/65.5 74/68 71/64 66.5/58.5 61/53 79/77 8.2/4.1
EX-600CKL

W/L

66.5/65 74/68 70/64 66.5/59 61/53.5 79/77 9.6/4.4
EX-750CKL

W/L

66.5/65 74/68 70/64 67/60 61/54 79/77 12/4.4
PLEASE NOTE THAT THESE INFORMATIONS MAY BE CHANGED WITHOUT NOTICE